Links

Emergency Lights - Industrial - AR


Shown in Standard Beige Finish

The AR Series is equipped with a refillable lead
acid battery, providing 8 to 12 years of service in
ambient temperatures ranging from 32° to 105°F.

Dimensions

AR

Height: 16.0"
Width: 14.3"
Depth: 5.9"



Series Features

  • Integrated Solid State System
  • Multi-Rate, Controlled, Automatic Charger
  • Fused AC Input & DC Output Circuit Protection
  • Low-Voltage Battery Cutoff
  • Brownout Sensitivity
  • Dual-Voltage Transformer for 120/277 VAC Operation
  • Maximum Input Rating
    120VAC 60 Hz 0.35 Amps
    277VAC 60 Hz 0.15 Amps
  • PAR-36 Sealed Beam Lamps, 6-Volt – 25-Watt
  • Refillable Lead Acid Battery
  • 32°–105°F Operating Range
  • 6-Volt Operation
  • 8–12 Year Operating Life
  • Rugged 20-Gauge Steel Housing
  • Top End Battery Access
  • Keyhole Mount Standard or Order Shelf No. 23
  • Beige Powder-Coat Finish Standard
  • Test Switch
  • Red (Power On) & Green (Trickle Charge) LED Indicators
  • UL Listed

Unit Information

Model
Number

Std.
Lamp
Watt

Watts per Hour

Replacement
Battery

1.5

2

3

4

5

6

7

8

2AR6L40†

25

120

90

60

45

36

30

26

23

(1) L640
H2AR6L40†
20

120

90

60

45

36

30

26

23

(1) L640
†Chicago Code Approved
Illumination is rated to 87.5% of nominal system voltage and recharge to full capacity within 24 hours. NEC requires 1.5 hours of emergency illumination.

Options
Add Suffix to Catalog Number

-GY Industrial Grey Finish
-P2 Cord & Plug for 120VAC Input
-QC Quik-Chek™ Remote Test & Time Delay
-TD Time Delay - Adjusts 1-60 min.
-** Special Lamp Wattage



Ordering Information

H

2

AR
6
L
40
-P2
Halogen Lamp Prefix

Lamp Heads on Unit
(0,1,2,3)

Series
DC Battery Voltage
Battery Type
(L - Lead Acid)
Battery Amp/Hour
Options
 