Emergency Lights - Commercial - BBEM-6

Dimensions

BBEM-6

Height: 5.0"
Width: 16.0"
Depth: 4.5"

 


Series Features

  • Integrated Solid State System
  • Multi-Rate, Controlled, Automatic Charger
  • Lock Out (Automatic Battery Connect)
  • Low-Voltage Battery Cutoff
  • Brownout Sensitivity
  • Dual-Voltage Transformer for
    120/277 VAC Operation
  • Maximum Input Rating
    120VAC 60 Hz 0.20 Amps /277VAC 60 Hz 0.20 Amps
  • High-Intensity Tungsten Lamps
  • Sealed Lead Calcium Battery
  • 6-Volt Operation
  • Maintenance-Free
  • Compact Design
  • Injection-Molded Thermoplastic Housing
  • High-Impact, Off-White Finish
  • Red (Power On) LED Indicator
  • Test Switch
  • Damp Location
  • UL Listed

Unit Information

Model
Number

Std.
Lamp
Watt

Watts per Hour

Replacement
Battery

1.5

2

3

4

5

6

7

8

BBEM-6

6

12

9

6

-

-

-

-

-

(1) S65

BBEM-9

9

22

16

14

10

-

-

-

-

(1) S68

Illumination is rated to 87.5% of nominal system voltage and recharge to full capacity within 24 hours. NEC requires 1.5 hours of emergency illumination.

Options
Add Suffix to Catalog Number

-BLK Black Finish
-P2 Cord & Plug for 120 VAC Input
-SD Self Diagnostic

Ordering Information

BBEM-6

Series