Lifelight Mini-UPS System
Emergency Lighting Inverter
Single Phase, 500 - 3000 VA
The Lifelight Mini-UPS is a low cost, single phase, space saving, central
lighting inverter that replaces older, larger and higher cost cabinets.
The Lifelight Mini-UPS integrated solid-state technology reduces maintenance
time of critical egress lighting, making the Lifelight Mini-UPS more
efficient and effective in keeping your system lit when you need it.
The small footprint of the Lifelight Mini-UPS allows for better utilization of
your floor space. The front access control panel also makes it easier for
maintenance.
The Lifelight Mini-UPS is a true on-line system, providing 90 minutes of
battery time for HID, fluorescent and incandescent lamp applications.

ELECTRICAL SPECIFICATIONS
Power Rating................................500, 750, 1000, 1250, 1500, 2000 and 3000 VA
Input Voltage .................................................................120, 208, 240 or 277 VAC
Output Voltage........................................................120, 240, 277 or 120/240 VAC
Output Frequency .............................................................................60 Hz. +/- 1%
Output Voltage Regulation .....+/- 3% for all loads and for Battery Discharge mode
Output Wave Form .......................................Sinewave <5% with 100% linear load
Output Protection .................................Current limiting and short circuit protection
Efficiency ....................................................................................................... >85%
Battery ....................................................Sealed, Maintenance-Free (AGM) Battery
Recharge Time ..............................................Recharge Time per UL 924 Standards
ENVIRONMENTAL SPECIFICATIONS
Humidity .......................................................................0 - 95% RH non-condensing
Operating Temperature......................................... -32°F to +104°F (0°C to +40°C)
Operating Altitiude..................................................Up to 6,000 feet (1,829 meters)
Non-operating ......................................................Up to 10,000 feet (3,048 meters)
Safety Agencies ..............................................................Listed to UL 924 Standard
STANDARD FEATURES |
- Low Profile Compact Cabinet
- 90 Minutes Battery Back-up
- AC Power ON Indicator
- Battery ON Indicator = AC Line Switch
- Charger ON Indicator = Test Button
- DC Battery Switch
|
FACTORY OPTIONS |
- Output Circuit Breakers (OCB) available in
increments of 1, 3, 6, 9 or 12
- Normally On Load (NOL)
- Normally Off Load (NOFFL)
- Maintenance By-Pass Switch (MBYP)
- 50 or 60 Hz
- Three Phase Configuatations
- Factory Start Up (TOS)
- Extended Warranty (EW)
- Outdoor or Harsh Environment Cabinets
|
Lifelight UPS System
Emergency Lighting Inverter
Single Phase, 3 - 18kVA
Lifelight 3PH-UPS System
Emergency Lighting Inverter
Three Phase, 15 - 50kVA
The Lifelight UPS and 3PH-UPS systems use DSP/PWM inverter technology.
This guarantees that no matter what lamp application is being used,
whether HID, fluorescent or incandescent, this is the on-line system to
meet your requirements.
The Lifelight UPS and 3PH-UPS systems are also available for harsh
environments that exist in industrial applications. The systems can be
housed in NEMA 3R or a totally enclosed 4X or 12X cabinet.
Location of the units is no longer a factor with the Lifelight UPS and 3PHUPS
systems. The enclosure and the monitoring package allows the
enduser to select a site either indoor or outdoor, with control and self-diagnostic
capabilities.
The Lifelight UPS and 3PH-UPS systems feature a hydrogen off-gassing
termination switch option. When the facility exhaust fan stops, the battery
charger will stop charging, but the inverter will continue to operate and
provide power to the load with full battery back-up.
ELECTRICAL SPECIFICATIONS
Power Rating.....................................................3, 5, 7.5, 10, 12.5, 15 or 18 kVA
Input Voltage .............................................................120, 208, 240 or 277 VAC
Input Voltage Range .......................................................................+10%, -15%
Output Voltage ...........................................120, 208, 240, 277 or 120/240 VAC
Output Frequency .........................................................................60 Hz. +/- 5%
Output Voltage Regulation ...........................................................+/- 2% Typical
Output Wave Form ..................................Sinewave <5% with 100% linear load
Crest Factor ....................................................................................2.5:1 Typical
Input Protection ........................................................Input Main Circuit Breaker
Output Protection ...................................................Output Main Circuit Breaker
Efficiency .................................................................................................. >92%
Battery ................................................Sealed, Maintenance-Free (AGM) Battery
Recharge Current................................................Conforms to UL 924 Standards
External Battery ..............Provision for hardwire connection of external battery
cabinets or DC source
Surge Protection ............The unit will protect itself and the load against surges
as defined in ANSI/IEEE C62.45, Categories A & B.
Output Transformer ............................................Shielded, isolation transformer
Isolation ................................................................................Complete from line
ENVIRONMENTAL SPECIFICATIONS
Humidity ..................................................................5 - 95% RH non-condensing
Operating Temperature ................................... -32°F to +104°F (0°C to +40°C)
Storage Temperature ..........................................-4°F to 140°F (-20°C to 60°C)
Audible Noise .................................... <58dB Measured on Response Curve "A"
Safety Agencies .......................................................Listed to UL 924 Standard
STANDARD FEATURES |
- Reliability (200,000 Hrs.)
- Energy Star Rated - TP1
- Industrial Application
- 90 Minutes Battery Back-up
- Front Service Access
- DSP/PWM Inverter
- Proven Non-linear Load Capability
- Incandescent, Fluorescent, HID Compatible
|
FACTORY OPTIONS |
- Maintenance By-Pass Switch (MBYP)
- Outdoor or Harsh Environment Cabinets
- "Hydrogen Off-Gassing Termination"
- Output Circuit Breakers
- Normally-Off Output Circuit Breakers
- Seismic Rated Bracket
- Normally - Off Output
- Remote Shutdown
- Remote Panel
- Normally - Off "Hold-On"
- Factory Start Up (TOS)
- Extended Warranty (EW)
|
Lifelight 3PH-UPS System
Emergency Lighting Inverter
Three Phase, 15 - 50kVA

ELECTRICAL SPECIFICATIONS
Power Rating .............................................................................15, 30 or 50kVA
Input Voltage ...........................................................208Y/120 or 480Y/277 VAC
Input Voltage Range .......................................................................+10%, -15%
Output Voltage ........................................................208Y/120 or 480Y/277 VAC
Output Frequency ........................................................................60 Hz. +/- 5%
Output Voltage Regulation ..........................................................+/- 2% Typical
Output Wave Form ...................................Sinewave<5% with 100% linear load
Crest Factor ....................................................................................2.5:1 Typical
Input Protection ........................................................Input Main Circuit Breaker
Output Protection ...................................................Output Main Circuit Breaker
Efficiency ................................................................................................. <92%
Battery ...............................................Sealed, Maintenance-Free (AGM) Battery
Recharge Current ..............................................Conforms to UL 924 Standards
External Battery ..........................Provision for hardwire connection of external
battery cabinets or DC source.
Surge Protection............The unit will protect itself and the load against surges
as defined in ANSI/IEEE C62.45, Categories A & B.
Output Transformer ............................................Shielded, isolation transformer
Isolation ...............................................................................Complete from line
ENVIRONMENTAL SPECIFICATIONS
Humidity...................................................................................5 - 95% RH non-condensing
Operating Temperature............................................................-32°F to +104°F (0°C to +40°C)
Storage Temperature ..............................................................-4°F to 140°F (-20°C to 60°C)
Audible Noise ..........................................................................<58dB Measured on Response Curve "A"
Safety Agencies ......................................................................Listed to UL 924 Standard
STANDARD FEATURES |
- Reliability (200,000 Hrs.)
- Energy Star Rated - TP1
- Industrial Application
- 90 Minutes Battery Back-up
- Front Service Access
- DSP/PWM Inverter
- Proven Non-linear Load Capability
- Incandescent, Fluorescent, HID Compatible
|
FACTORY OPTIONS |
- Maintenance By-Pass Switch (MBYP)
- Outdoor or Harsh Environment Cabinets
- "Hydrogen Off-Gassing Termination"
- Output Circuit Breakers
- Normally-Off Output Circuit Breakers
- Seismic Rated Bracket
- Normally - Off Output
- Remote Shutdown
- Remote Panel
- Normally - Off "Hold-On"
- Factory Start Up (TOS)
- Extended Warranty (EW)
|
|