Life Safety Code (NFPA 101)
SECTION 7.9
EMERGENCY LIGHTING
7.9.1 General
7.9.1.1* Emergency lighting facilities for means of egress shall be
provided in accordance with Section 7.9 for the following:
(1) Buildings or structures where required in Chapter 11 through
Chapter 42.
7.9.1.2 For the purposes of 7.9.1.1, exit access shall include only
designated stairs, aisles, corridors, ramps, escalators, and
passageways leading to an exit. For purposes of 7.9.1.1, exit discharge
shall include only designated stairs, aisles, corridors, ramps, escalators,
and passageways leading to a public way.
7.9.1.3 Where maintenance of illumination depends on changing from
one energy source to another, a delay of not more than 10 seconds
shall be permitted.
7.9.2 Performance of Systems
7.9.2.1* Emergency illumination shall be provided for not less than
1-1/2 hours in the event of failure of normal lighting. Emergency lighting
facilities shall be arranged to provide initial illumination that is not less
than an average of 10.8 lux (1 ft.-candle) and, at any point , not less than
1.1 lux (0.1 ft.-candle), measured along the path of egress at floor level.
Illumination levels shall be permitted to decline to not less than an
average of 6.5 lux (0.6 ft.-candle) and, at any point, not less then 6.5 lux
(0.06 ft.-candle) at the end of the 1-1/2 hours. A maximum-to-minimum
illumination uniformity ratio of 40 to 1 shall not be exceeded.
7.9.2.2* The emergency lighting system shall be arranged to provide
the required illumination automatically in the event of any interruption
of normal lighting due to any of the following:
(1) Failure of a public utility or other outside electrical power supply.
(2) Opening of a circuit breaker or fuse.
(3) Manual act(s), including accidental opening of a switch
controlling normal lighting facilities.
7.9.2.4* Battery-operated emergency lights shall use only reliable
types of rechargeable batteries provided with suitable facilities for
maintaining them in properly charged condition. Batteries used in
such lights or units shall be approved for their intended use and shall
comply with NFPA 70, National Electrical Code®.
7.9.2.5 The emergency lighting system shall be either continuously in
operation or shall be capable of repeated automatic operation without
manual intervention.
7.9.3 Periodic Testing of Emergency Lighting Equipment
7.9.3.1.1 Testing of required emergency lighting systems shall be
permitted to be conducted as follows:
(1) Functional testing shall be conducted at 30-day intervals for not
less then 30 seconds.
(2) Functional testing shall be conducted annually for not less than
1-1/2 hours if the emergency lighting system is battery powered.
(3) The emergency lighting equipment shall be fully operational for
the duration of the tests required by 7.9.3.1.1(1) and 7.9.3.1.1(2).
(4) Written records of visual inspections and tests shall be kept by
the owner for inspection by the authority having jurisdiction.
SECTION 7.10
MARKING MEANS OF EGRESS
7.10.1 General
7.10.1.1 Where Required. Means of egress shall be marked in
accordance with Section 7.10 where required in Chapter 11 through
Chapter 42.
7.10.1.2* Exits. Exits, other than main exterior exit doors that obviously
and clearly are identifiable as exits, shall be marked by an approved
sign that is readily visible from any direction of exit access.
7.10.1.5 Exit Access
7.10.1.5.1 Access to exits shall be marked by approved readily visible
signs in all cases where the exit or way to reach the exit is not readily
apparent to the occupants. 7.10.1.5.2* New sign placement shall be such that no point in an exit
access corridor is in excess of the rated viewing distance or 30 m
(100 ft), whichever is less, from the nearest sign.
7.10.2* Directional Signs. A sign complying with 7.10.3 with a
directional indicator showing the direction of travel shall be placed in
every location where the direction of travel to reach the nearest exit is
not apparent.
7.10.3* Sign Legend
7.10.3.1 Signs required by 7.10.1 and 7.10.2 shall read as follows in
plainly legible letters, or other appropriate wording shall be used: EXIT.
7.10.5 Illumination of Signs
7.10.5.1* General.
Every sign required by 7.10.1.2 or 7.10.1.5, other
than where operations or processes require low lighting levels, shall
be suitably illuminated by a reliable light source. Externally and
internally illuminated signs shall be legible in both the normal and
emergency lighting mode.
7.10.6 Externally Illuminated Signs
7.10.6.1.1 Externally illuminated signs required by 7.10.1 and 7.10.2,
other than approved existing signs, unless otherwise provided in
7.10.6.1.2, shall read EXIT, or other appropriate wording shall be
used in plainly legible letters sized as follows:
(1) For new signs, the letters shall be not less than 150 mm (6 in.)
high, with the principal strokes of letters not less then 19 mm
(3/4 in.) wide.
(2) For existing signs, the required wording shall be permitted to
be in plainly legible letters not less than 100 mm (4 in.) high.
(3) The word EXIT shall be in letters of a width not less than 51 mm
(2 in.), except the letter I, and the minimum spacing between
letters shall be not less then 9.5 mm (3/8 in.).
(4) Sign legend elements larger than the minimum established in
7.10.6.1.1(1) through 7.10.6.1.1(3) shall use letter widths,
strokes, and spacing in proportion to their height.
7.10.6.2* Size and Location of Directional Indicator
7.10.6.2.1 Directional indicators, unless otherwise provided in
7.10.6.2.2, shall comply with the following:
(1) The directional indicator shall be located outside of the EXIT
legend, not less than 9.5 mm (3/8 in.) from any letter.
(2) The directional indicator shall be of a chevron type…
7.10.6.3* Level of Illumination
Externally illuminated signs shall be illuminated by not less then 54 lux
(5 ft.-candles) at the illuminated surface and shall have a contrast ratio
of not less then 0.5.
7.10.7 Internally Illuminated Signs
7.10.7.1 Listing. Internally illuminated signs shall be listed in
accordance with UL 924, Standard for Safety Emergency Lighting
and Power Equipment, unless they meet one of the following criteria:
(1) They are approved existing exit signs.
(2) They are existing signs having the required wording in legible
letters not less then 100 mm (4 in.) high.
(3) They are signs that are in accordance with 7.10.1.3 and
7.10.1.6.
7.10.9 Testing and Maintenance
7.10.9.1 Inspection.
Exit signs shall be visually inspected for
operation of the illumination sources at intervals not to exceed 30
days, or shall be periodically monitored inaccordance with 7.9.3.1.3.
7.10.9.2 Testing.
Exit signs connected to or provided with a batteryoperated
emergency illumination source, where required in 7.10.4,
shall be tested and maintained in accordance with 7.9.3.
Excerpted from
Life Safety Code 2003
(Pgs. 101–67 to 101–69)
|
|