National Electric Code (NFPA 70)
Article 700 – Emergency Systems
I. GENERAL
700-1. Scope
Emergency systems are intended to automatically supply
illumination or power, or both, to designated areas and
equipment in the event of failure of the normal supply or in the
event of accident to elements of a system intended to supply,
distribute, and control power and illumination essential for
safety to human life.
700-3. Equipment Approval
All equipment shall be approved for use on emergency systems.
700-4. Tests and Maintenance
(A) Conduct or Witness Test
The authority having jurisdiction shall conduct or witness a test
on the complete system upon installation and periodically
afterward.
(B) Tested Periodically
Systems shall be tested periodically on a schedule acceptable
to the authority having jurisdiction to assure their maintenance
in proper operating condition.
(C) Battery Systems Maintenance
here battery systems or unit equipment are involved…the
authority having jurisdiction shall require periodic maintenance. (D) Written Record
A written record shall be kept of such tests and maintenance.
(E) Testing Under Load
Means for testing all emergency lighting and power systems
during maximum anticipated load conditions shall be provided.
700-5. Capacity
(A) Capacity and Rating
An emergency system shall have adequate capacity and rating
for all loads to be operated simultaneously. The emergency
system shall be suitable for the maximum available fault
current at its terminals.
II. CIRCUIT WIRING
700-9. Wiring, Emergency System
(B) Wiring
Wiring of two or more emergency circuits supplied from the
same source shall be permitted in the same raceway, cable
box or cabinet. Wiring from an emergency source or
emergency source distribution overcurrent protection to
emergency loads shall be kept entirely independent of all other
wiring and equipment, unless otherwise permitted in
(1) through (4):
(1) Wiring from the normal power source located in
transfer equipment enclosures
(2) Wiring supplied from two sources in exit or emergencyluminaires (lighting fixtures)
(3) Wiring from two sources in a common junction box,
attached to exit or emergency luminaires (lighting
fixtures)
(4) Wiring within a common junction box attached to unit
equipment, containing only the branch circuit supplying
the unit equipment and the emergency circuit supplied
by the unit equipment. III. SOURCES OF POWER
700-12. General Requirements
Current supply shall be such that, in the event of failure of the
normal supply to, or within, the building…emergency lighting,
emergency power, or both will be available within the time
required for the application, but not to exceed 10 seconds.
(A) Storage Battery
Storage batteries used as source of power for emergency
systems shall be of suitable rating and capacity to supply and
maintain the total load for a period of 1-1/2 hours minimum,
without the voltage applied to the load falling below 87-1/2
percent of normal.
Batteries…shall be designed and constructed to meet the
requirements of emergency service and shall be compatible
with the charger for that particular installation.
For a sealed battery, the container shall not be required to be
transparent. However, for the lead acid battery that requires
water additions, transparent or translucent jars shall be
furnished. Automotive-type batteries shall not be used.
An automatic battery-charging means shall be provided.
(E) Unit Equipment
Individual unit equipment for emergency illumination shall
consist of (1) a rechargeable battery; (2) a battery charging
means; (3) provisions for one or more lamps mounted on the
equipment, or shall be permitted to have terminals for remote
lamps, or both; and (4) a relaying device arranged to energize
the lamps automatically upon failure of the supply to the unit
equipment. The batteries shall be of suitable rating and
capacity to supply and maintain at not less than 87-1/2
percent of the nominal battery voltage for the total lamp load
associated with the unit for a period of at least 1-1/2 hours…
Unit equipment shall be permanently mounted in place (i.e., not
portable) and shall have all wiring to each unit installed in
accordance with the requirements of any of the wiring methods
in Chapter 3. Flexible cord- and plug-connection shall be
permitted, provided that the cord does not exceed 3 feet…in
length. The branch circuit feeding the unit equipment shall be
the same branch circuit as that serving the normal lighting in
the area and connected ahead of any local switches…
IV. EMERGENCY SYSTEM CIRCUITS FOR
LIGHTING & POWER
700-15. Loads on Emergency Branch Circuits
No appliances and no lamps, other than those specified as
required for emergency use, shall be supplied by emergency
lighting circuits.
700-16. Emergency Illumination
Emergency illumination shall include all required means of
egress lighting, illuminated exit signs, and all other lights
specified as necessary to provide required illumination.
Emergency lighting systems shall be so designed and installed
that the failure of any individual lighting element, such as the
burning out of a light bulb, cannot leave in total darkness any
space that requires emergency illumination.
Where high-intensity discharge lighting such as high- and lowpressure
sodium, mercury vapor, and metal halide is used as
the sole source of normal illumination, the emergency lighting
system shall be required to operate until normal llumination
has been restored.
Excerpted from
National Electrical Code 2002
(Pgs. 555–559)
|
|