EFB / EPLB
Emergency Fluorescent Ballast

An affordable alternative to conventional emergency lighting, the EFB Series is a fluorescent ballast, which enhances existing AC fixtures by illuminating 1 or 2 lamps during a power failure.

Dimensions

EFB40-2
Height: 1.5″
Length: 13.125″
Width: 2.375″
Mtg. Ctr.: 12.75″

ALL OTHERS
Height: 1.5″
Length: 9.5″
Width: 2.375″
Mtg. Ctr.: 9.0″

 

Series Features

  • Solid State Charger
  • Dual-Voltage Transformer for 120/277 VAC Operation
  • Maximum Input Rating
    120VAC 60 Hz 4.0 Watt
    277VAC 60 Hz 4.0 Watt
  • For Use on Single or Double Lamps
  • Illuminates Rapid Start, Instant Start, High Output, Slim Line, Circline, U-Shaped or Compact Lamps
  • Sealed Nickel Cadmium Battery
  • Maintenance-Free
Emergency Ballast
  • Converts Fluorescent Fixtures to Emergency Lighting
  • Provides 1.5-Hour Illumination for Single or Double Lamps
  • Completely Self-Contained Inside or Above Lighting Fixture
  • Compact Steel Housing
  • Convenient Length Lead Wires
  • Test Switch
  • Red (Power On) Indicator
  • Operating Range: 50°–140°F
  • Warranty: 2–5 Years
  • UL Listed

Unit Information

Linear Lamps

Lamps Operated

Qty.

EFB40

500 Lumens

EFB80

700 Lumens

EFB40-2

1300 Lumens

EPLB13

650 Lumens

EPLB26

650 Lumens

EPLB42

650 Lumens

2′-4′ Rapid, Instant Energy
Saving, T8 and T12
1

X

X

X

2′-4′ Rapid, Instant Energy Saving, T8 and T12, HO & VHO
2

X**

X**

5′-8′ Rapid, Instant
Energy Saving, T8 and T12, HO & VHO
1

X

X

20W-40W Circline
1

X

X

X

20W-40W Circline
2

X

X

 

Compact Lamps

Lamps Operated

Qty.

EFB40

500 Lumens

EFB80

700 Lumens

EFB40-2

1300 Lumens

EPLB13

650 Lumens

EPLB26

650 Lumens

EPLB42

650 Lumens

5-, 7-, 9- & 13-Watt Twin Tube (2 pin)
1

X

9W–13W USA Quad Tube(2
pin)
1

X

18W-26W Quad Tube (2 pin)*
1 or 2

X

10W-26W Quad Tube (4 pin)
1

X

18W-39W Long Compact
1

X

40-Watt Biax
1

X

X

50-Watt Biax
1

X

55-Watt Biax
1

X

18W-26W Triple Tube (4 pin)
1 or 2

X

32W-42W Triple Tube (4 pin)
1

X

*22- & 28-Watt 15 mm lamps are not compatible.
**Note: Two-lamp emergency is not possible with all electronic ballasts.
Consult customer service for specific ballast compatibility.

Options - Add Suffix to Catalog Number

-SuffixOption Description
-FCFlex Cord
-RTSKRemote Test Switch Kit (EFB Series)
-TMKTop Mount Kit

Ordering Information

EFB40
-TMK
Model
Options