Big Beam Emergency Systems, Inc.Exit SignsHand Lanterns
Big Beam Emergency Systems, Inc.Inverter SystemsEmergency Lighting
Big Beam Emergency Systems, Inc.

Big Beam Emergency Systems, Inc.
About Big Beam
The Big Beam Difference
Lifetime Warranty
Literature Request
Quotation Request
Representative Locations
Product Catalog
Self-Test/Self-Diagnostic
UPS Systems
Technical Data
Energy Star Products
Instruction Sheets
Terms and Conditions
Contact Us
Links
Links

Self-Test/Self-Diagnostic Options

Unit Information - Available on the following units by using the -SD suffix

Model Number

Std. Lamp Wattage

1.5

2

3

4

5

6

7

8

Battery

Shape

2ET6S5

6

12

9

6

-

-

-

-

-

(1) S65

Rect.

2ET6S8

9

18

14

9

7

-

-

-

-

(1) S68

Rect.

2ET6S8-8

8

18

14

9

7

-

-

-

-

(1) S68

Round

H2ET6S10 †

12

32

24

16

12

10

8

7

6

(1) S610SL

Round

H2ET6S16 †

12

45

36

24

18

14

12

10

9

(2) S68

Round

H2ET12S7 †

12

36

27

18

14

11

9

8

7

(2) S68

Round

2ET6N4

6

12

9

6

-

-

-

-

-

(1) N64F

Rect.

2ET6N7

9

25

18

14

9

-

-

-

-

(1) N67F

Rect.

2ET12N4

9

25

18

14

9

-

-

-

-

(2) N64F

Rect.

2ET12N7

9

50

36

24

18

14

12

10

9

(2) N67F

Rect.

H2ET6N4

6

12

9

6

-

-

-

-

-

(1) N64F

Rect.

H2ET6N7 †

12

25

18

14

9

-

-

-

-

(1) N67F

Rect.

H2ET12N4 †

12

25

18

14

9

-

-

-

-

(1) N64F

Round

H2ET12N7 †

12

50

36

24

18

14

12

10

9

(2) N67F

Round

2RL6S5-R

6

12

9

6

-

-

-

-

-

(1) S65

Round

2RL6S5-PH

6

12

9

6

-

-

-

-

-

(1) S65

Rect.

2RL6S8-R

9

18

14

9

7

-

-

-

-

(1) S68

Round

2RL6S8-PH

9

18

14

9

7

-

-

-

-

(1) S68

Rect.

2RL6S10-R

9

32

24

16

12

-

-

-

-

(1) S610SL

Round

2RL6S10-PH

9

32

24

16

12

-

-

-

-

(1) S610SL

Rect.

H2RL6S10 †

12

32

24

16

12

-

-

-

-

(1) S610SL

Round

2RL6N4-R

6

12

9

6

-

-

-

-

-

(1) N64F

Round

2RL6N4-PH

6

12

9

6

-

-

-

-

-

(1) N64F

Rect.

2RL6N7-R

9

25

18

14

9

-

-

-

-

(1) N67F

Round

2RL6N7-PH

9

25

18

14

9

-

-

-

-

(1) N67F

Rect.

H2RL6N7 †

12

25

18

14

9

-

-

-

-

(1) N67F

Round

2BR6S8

8

18

14

9

7

-

-

-

-

(1) S68

 

H2BR6S10 †

12

32

24

16

12

10

8

7

6

(1) S610SL

 

2BR6S16

8

45

36

20

15

12

10

9

8

(2) S68

 

2BR6S20

8

64

50

32

24

19

16

14

12

(2) S610SL

 

2BR6S36

8

100

75

50

38

30

25

21

18

(1) S636

 

H2BR12S7 †

12

36

27

18

14

11

9

8

7

(2) S68

 

H2BR12S10 †

12

60

45

36

23

18

15

13

11

(2) S610SL

 

H2BR12S15 †

12

100

75

50

38

30

25

21

18

(1) S1215

 

2SC6S8

8

18

14

9

7

-

-

-

-

(1) S68

 

2SC6S10

8

32

24

16

12

10

8

7

6

(1) S610SL

 

2SC6S16

8

45

36

20

15

12

10

9

8

(2) S68

 

2SC6S20

8

64

50

32

24

19

16

14

12

(2) S610SL

 

2SC6S36

8

100

75

50

38

30

25

21

18

(1) S636

 

H2SC6S10 †

12

32

24

16

12

10

8

7

6

(2) S610SL

 

H2SC6S16 †

12

45

36

20

15

12

10

9

8

(2) S68

 

H2SC6S20 †

12

64

50

32

24

19

16

14

12

(2) S610SL

 

H2SC6S36 †

12

100

75

50

38

30

25

21

18

(1) S636

 

H2SC12S7 †

12

36

27

18

14

11

9

8

7

(2) S68

 

H2SC12S10 †

12

60

45

30

23

18

15

13

11

(2) S610SL

 

H2SC12S15 †

12

100

75

50

38

30

25

21

18

(1) S1215

 

2SC6N7

8

25

18

14

9

-

-

-

-

(1) N64F

 

2SC12N7

18

50

36

24

18

14

12

10

9

(2) N67F

 

H2SC6N4

6

12

9

6

-

-

-

-

-

(1) N64F

 

H2SC6N7 †

12

25

18

14

9

-

-

-

-

(1) N67F

 

H2SC12N4 †

12

25

18

14

9

-

-

-

-

(2) N64F

 

H2SC12N7 †

12

50

36

24

18

14

12

10

9

(2) N67F

 

2IL6S20 †

25

64

50

-

24

-

-

-

12

(2) S610SL

 

2IL6S36 †

25

100

75

-

75

-

-

-

18

(1) S636

 

2IL6L40 †

25

120

90

60

45

36

30

26

23

(1) L640

 

2IL12S10 †

25

60

45

-

23

-

-

-

11

(2) S610SL

 

2IL12S15 †

25

100

75

-

38

-

-

-

18

(1) S1215

 

2IL12S20 †

25

120

90

-

45

-

-

-

23

(1) S1220

 

2IL12S36 †

25

200

150

-

76

-

-

-

36

(2) S636

 

2AR6L40 †

25

120

90

60

45

36

30

26

23

(1) L640

 

H2AR6L40 †

20

120

90

60

45

36

30

26

23

(1) L640

 

2SC6S8

8

18

14

9

7

-

-

-

-

(1) S68

 

2SC6S10

8

32

24

16

12

10

8

7

6

(1) S610SL

 

2SC616

8

45

36

20

15

12

10

9

8

(2) S68

 

2SC6S20

8

64

50

32

24

19

16

14

12

(2) S610SL

 

2SC6S36

8

100

75

50

38

30

25

21

18

(1) S636

 

H2SC6S10 †

12

32

24

16

12

10

8

7

6

(2) S610SL

 

H2SC6S16†

12

45

36

20

15

12

10

9

8

(2) S68

 

H2SC6S20 †

12

64

50

32

24

19

16

14

12

(2) S610SL

 

H2SC6S36 †

12

100

75

50

38

30

25

21

18

(1) S636

 

H2SC12S7 †

12

36

27

18

14

11

9

8

7

(2) S68

 

H2SC12S10 †

12

60

45

30

23

18

15

13

11

(2) S610SL

 

H2SC12S15 †

12

100

75

50

38

30

25

21

18

(1) S1215

 

2SC6N7

8

25

18

14

9

-

-

-

-

(1) N64F

 

2SC12N7

18

50

36

24

18

14

12

10

9

(2) N67F

 

H2SC6N4

6

12

9

6

-

-

-

-

-

(1) N64F

 

H2SC6N7 †

12

25

18

14

9

-

-

-

-

(1) N67F

 

H2SC12N4 †

12

25

18

14

9

-

-

-

-

(2) N64F

 

H2SC12N7 †

12

50

36

24

18

14

12

10

9

(2) N64F

 

Life Safety Code (NFPA 101)

SECTION 7.9

EMERGENCY LIGHTING

7.9.3 Periodic Testing of Emergency Lighting Equipment

7.9.3.1 Required emergency lighting systems shall be tested in accordance with one of the three options offered by 7.9.3.1.1, 7.9.3.1.2, 7.9.3.1.3.

7.9.3.1.1 Testing of required emergency lighting systems shall be permitted to be conducted as follows:

(1) Functional testing shall be conducted at 30-day intervals for not less than 30 seconds.

(2) Functional testing shall be conducted annually for not less than 1½ hours if the emergency lighting system is battery powered.

(3) The emergency lighting equipment shall be fully operational for the duration of the test required by 7.9.3.1.1(1) and 7.9.3.1.1(2).

(4) Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

7.9.3.1.2 Testing of required emergency lighting systems shall be permitted to be conducted as follows:

(1) Self-testing / self-diagnostic battery-operated emergency lighting equipment shall be provided.

(2) Self-testing / self-diagnostic battery-operated emergency lighting equipment shall automatically perform not less than once every 30 days a test for not less than 30 seconds and a diagnostic routine.

(3) Self-testing / self-diagnostic battery-operated emergency lighting equipment shall indicate failures by a status indicator.

(4) A visual inspection shall be performed at intervals not exceeding 30 days.

(5) Functional testing shall be conducted annually for not less than 1½ hours.

(6) Self-testing / self-diagnostic battery-operated emergency lighting equipment shall be fully operational for the duration of the 1½ hour test.

(7) Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

7.9.3.1.3 Testing of required emergency lighting systems shall be permitted to be conducted as follows:

(1) Computer-based, self-testing / self-diagnostic battery-operated emergency lighting equipment shall be provided.

(2) The emergency lighting equipment shall automatically perform not less than once every 30 days a test for not less than 30 seconds and a diagnostic routine.

(3) The emergency lighting equipment shall automatically perform annually a test for not less than 1½ hours.

(4) The emergency lighting equipment shall be fully operational for the duration of the tests required by 7.9.3.1.3(2) and 7.9.3.1.3(3).

(5) The computer-based system shall be capable of providing a report of the history of the tests and failures at all times.

Exerpted from
Life Safety Code 2003
Page 101-67


Print this catalog page (PDF)