Emergency Lights - Industrial - TCL

Shown in Standard Beige Finish with Wood Grain Panel
Rugged steel
construction is
combined with
state-of-the-art
LED status indicators,
making
the
TCL Series an
ideal choice for
demanding industrial
applications. A
slide-out modular
control assembly
allows for quick
and
easy product
upgrades.
|
Dimensions
TCL
Height: 20.5"
Width: 18.5"
Depth: 8.5"
|
Series Features |
|
- Integrated Solid State System
- Three-Rate, Controlled, Automatic Charger
- Fused AC Input & DC Output Circuit Protection
- Low-Voltage Battery Cutoff
- Brownout Sensitivity
- Single-Voltage Transformer for 120VAC Operation
- Maximum Input Rating
120VAC 60 Hz 0.50 Amps
277VAC 60 Hz 0.23 Amps
|
|
- PAR-46 Sealed Beam Lamps STD Lamp: See Unit Information
|
|
- Refillable Lead Acid Battery
- 32°–105°F Operating Range
- 6- or 12-Volt Operation
- 8–12 Year Operating Life
|
|
- Rugged 20-Gauge Steel Housing
- Top End Battery Access
- Full-Length Piano Hinge with Lock Hasp
- Integral Carrying Handles
- Two-Tone Powder-Coat Finish (Beige & Cocoa) Standard
- Slide-Out Control Chassis
- Test Switch
- Battery Capacity Indicator: Incremental LED Panel
Indicates Current Battery Charge/Discharge Status
- Amber (AC On) LED Indicator
- UL Listed
|
| Order No. 22 Mounting Shelf |
Unit Information |
Model
Number
|
Std.
Lamp
Watt |
Watts per Hour |
Replacement
Battery |
|
|
25 |
|
(1) L640 |
| 2TC6L100† |
22 |
120 |
120 |
120 |
120 |
96 |
80 |
69 |
60 |
|
(1) L6100 |
| 2TC6L100DO† |
25 |
225 |
169 |
145 |
120 |
96 |
80 |
69 |
60 |
|
(1) L6100 |
| 2TC12L60† |
35 |
240 |
180 |
120 |
90 |
72 |
60 |
51 |
45 |
|
(1) L1260 |
| †Chicago Code Approved |
| Illumination is rated to 87.5% of nominal system voltage and recharge to full capacity within 24 hours. NEC requires 1.5 hours of emergency illumination. |
Options
Add Suffix to Catalog Number
|
| -277 |
277VAC Input |
| -BDS |
Battery Disconnect Switch |
| -GY |
Industrial Grey Finish |
| -P2 |
Cord & Plug for 120VAC Input |
| -QC |
Quik-Chek™ Remote Test & Time Delay |
| -TD |
Time Delay - Adjusts 1-60 min. |
| -** |
Special Lamp
Wattage |
|
 |
 |
 |
Ordering Information |
H |
2
|
|
|
|
60 |
-TD |
Halogen Lamp Prefix* |
Lamp Heads on Unit
(0,1,2,3) |
|
DC Battery Voltage
(6 - 6-Volt)
(12 - 12-Volt)
|
Battery Type
(S - Sealed)
(L - Lead Acid)
|
|
Options |
|
Print this catalog page (PDF)
|