Wiring Distance Chart
Wiring Distance (Measured in Feet) |
6 Volt |
|
12 Volt |
12 Ga |
10 Ga |
8 Ga |
6 Ga |
Total Watts
on Wire Run |
12 Ga |
10 Ga |
8 Ga |
6 Ga |
4 Ga |
89 |
141 |
225 |
357 |
6 |
356 |
566 |
900 |
1431 |
2276 |
66 |
106 |
168 |
268 |
8 |
267 |
424 |
675 |
1073 |
1707 |
59 |
94 |
150 |
238 |
9 |
237 |
377 |
600 |
954 |
1517 |
53 |
84 |
135 |
214 |
10 |
213 |
339 |
540 |
859 |
1366 |
44 |
70 |
112 |
178 |
12 |
178 |
283 |
450 |
715 |
1138 |
33 |
53 |
84 |
134 |
16 |
133 |
212 |
337 |
536 |
853 |
29 |
47 |
75 |
119 |
18 |
118 |
188 |
300 |
477 |
758 |
22 |
35 |
56 |
89 |
24 |
89 |
141 |
225 |
357 |
569 |
21 |
33 |
54 |
85 |
25 |
85 |
135 |
216 |
343 |
546 |
19 |
31 |
50 |
79 |
27 |
79 |
125 |
200 |
318 |
505 |
17 |
28 |
45 |
71 |
30 |
71 |
113 |
180 |
286 |
455 |
14 |
23 |
37 |
59 |
36 |
59 |
94 |
150 |
238 |
379 |
12 |
20 |
32 |
51 |
42 |
51 |
80 |
128 |
204 |
325 |
11 |
18 |
30 |
47 |
45 |
47 |
75 |
120 |
190 |
303 |
11 |
17 |
28 |
44 |
48 |
44 |
70 |
112 |
178 |
284 |
10 |
16 |
27 |
42 |
50 |
42 |
67 |
108 |
171 |
273 |
7 |
11 |
18 |
28 |
75 |
28 |
45 |
72 |
114 |
182 |
5 |
8 |
13 |
21 |
100 |
21 |
33 |
54 |
85 |
136 |
|
5 |
9 |
14 |
150 |
14 |
22 |
36 |
57 |
91 |
|
|
6 |
10 |
200 |
10 |
16 |
27 |
42 |
68 |
|
|
5 |
8 |
250 |
8 |
13 |
21 |
34 |
54 |
|
|
|
7 |
300 |
7 |
11 |
18 |
28 |
45 |
Maximum Voltage Drop 5%
Key to Longer Wire Runs
The Wiring Distance Chart gives the
maximum length of a given remote lamp
circuit, assume the entire remote load is
concentrated at the end of the wire run.
If remote lamp fixtures are uniformly
spaced along the circuit path (equal
watts spaced at equal distance), the
lengths in the table may be increased,
based on the chart and formula below:
# OF FIXTURES
2
|
3 |
4 |
5 |
6 |
N |
1.33 |
1.5 |
1.6 |
1.67 |
1.71 |
2N/(N+1) |
MULTIPLY FEET BY
For example, a 100-foot long, 12-volt,
remote lamp circuit has four 12-watt fixtures
spaced 25 feet apart. According to the
Wire Distance Chart, #8 Ga. wire would be
required for 48 total watts up to 112 feet,
to allow a 5% voltage drop or less.
However, since the fixtures are equal in
wattage and are spaced equally along the
circuit, the distance of 70 feet for #10 Ga.
wire can be multiplied by 1.6 (70 x 1.6 = 112),
so in this case up to a 112-foot wire run
with #10 Ga. wire would be acceptable.
Note: For systems operating at less
than 50 volts, the smallest permissible
wire size is #12 Ga. copper or equivalent
per NFPA70 (National Electrical Code),
Article 720-4. 
|